The essential role of static smoke barriers (SSB)

The essential role of static smoke barriers (SSB)

Smoke barrier screens prevent the spread of fire effluents inside a building in the event of a fire by containing and channelling the movement of smoke. 

During a fire, smoke containment screen systems maintain a smoke-free area and limit the spread of fire effluents inside a building in the event of a fire by containing and channelling the movement of smoke. 

These systems are widely used to support the safe evacuation of people from buildings and other structures and to reduce damage and financial losses due to smoke. They also facilitate firefighting by improving visibility, reduce temperatures under the roof, and slow the spread of fire. 

This is done by forming a barrier that creates a reservoir for smoke. This reservoir controls and limits the advance of smoke by channelling smoke in one predetermined direction to facilitate its evacuation and by slowing or preventing the circulation of smoke into other areas or voids. 

Applications

Static smoke barriers can be used in the following containment applications: 

  • Around smoke tanks  
  • To screen pipelines  
  • At the edge of voids 
  • Above empty spaces 
  • Around the periphery of open atriums 
  • Within corridors 
  • At storefronts 
  • To isolate escalators 
  • To isolate stairwells 
  • To isolate elevators 
  • Along railway tracks and train platforms 

What the standards say

All smoke barriers must comply with the standard EN 12101-1 (Smoke and heat control systems - Part 1: Specifications for smoke barriers), which specifies the product characteristics, methods for testing and evaluation, and compliance criteria for smoke barriers.  

All smoke containment screens must provide fire resistance stability at a constant temperature (600°C) over a set period of time or on a standardized time-temperature curve (ISO 834/EN 1363-1). 

Smoke barriers tested to a constant temperature stability time (D) must maintain their integrity for a defined time at 600°C. Barriers are classified in accordance with EN 13501-4 (Classification using data from fire resistance tests on components of smoke control systems). 

Table 1 – Normalized classes 

Classes  Temperature (°C)  Time (min) 
D600 30  600  30 
D600 60  600  60 
D600 90  600  90 
D600 120  600  120 
D600 A 600  Any duration beyond 120 min 

Table 2 – Classes for smoke barrier systems operating in high temperatures

Classes  Temperature (°C)  Time (min) 
DH 30  Normalized heating curve (ISO 834/EN 1363-1)  30 
DH 60  Same  60 
DH 90  Same  90 
DH 120  Same  120 
DHA  Same  Any duration beyond 120 min 

Meeting the standard

The Assessment and Verification of Constancy of Performance (AVCP), the Declaration of Performance (DoP), and the CE marking issued by Vetrotech Saint-Gobain for the PYROSWISS SBS smoke containment screen meet the various criteria defined within the framework of system 1, governed by Regulation 305/2011 of the European Parliament and Council (CPR 305/2011). 